RCM residual current type electric fire monitoring device
source:管理员 time:2018-10-19

  1 Overview of residual current electrical fire monitoring system

  The ARCM residual current type electrical fire monitoring device is installed in a 0.4kV low-voltage power distribution system to detect electrical parameters related to electrical fire hazards such as residual current and temperature in TN-CS, TN-S and local TT systems. When the monitoring device parameter in the protection line exceeds the alarm setting value, an alarm and control signal can be generated to eliminate the electrical fire hazard caused by the residual current. The product adopts RS485 bus for communication, and can be combined with other monitoring alarms, monitoring units or monitoring hosts to form a fire monitoring system. The centralized bus type information management mode or functional partition type information management mode can be selected according to user needs.

  Applicable to intelligent buildings, high-rise apartments, hotels, restaurants, commercial buildings, industrial and mining enterprises, national key fire-fighting units, petrochemicals, culture, education, health, finance, telecommunications, etc., in line with GB 14287.2-2005 "Electrical fire monitoring system Part 2: Residual current Standard for electrical fire monitoring detectors and GB 13955-2005 "Installation and operation of residual current operated protective devices".

  2 Residual current type electric fire monitoring system applicable environment

  Working temperature: -10 ° C ~ +55 ° C

  Storage temperature: -20 ° C ~ +70 ° C

  Relative humidity: ≤95% no condensation

  Altitude: ≤2500m

  Pollution degree: Class III, installation category: Level III

  3 Residual current type electric fire monitoring system product selection list



  4 Residual current type electric fire monitoring system product introduction

  4.1 ARCM100-Z monitoring detector

  4.1.1 Features

  ● It has various protection functions such as residual current protection, temperature protection, overvoltage protection, phase loss protection and overcurrent protection.

  ● Real-time measurement of the three-phase voltage, three-phase current, frequency, power, four-quadrant power, fundamental wave, total harmonic energy and other electrical parameters of the loop;

  ● Provide three-way switch input function, which can connect fire-fighting linkage signal and smoke alarm signal, realize high-reliability and realize remote control of fire-fighting system through device, forcibly cut off power supply at fault point;

  ● Relay protection output: It has the functions of alarm output and trip output, and can feedback the switch status to the fire protection system;

  ● Adopt advanced fieldbus communication technology, the upper computer management software can monitor the running status of the site in real time and issue alarm information in time;

  ● With event storage function, the alarm can record the time, type, parameter and phase sequence of the alarm. According to the alarm record, the power consumption of the site can be analyzed to provide a basis for eliminating the fault.

  ● Real-time temperature monitoring function, online detection of the sensor, sensor disconnection, short-circuit will send an alarm signal;

  ● Power-down protection function, when the monitoring device is in the alarm state, it will encounter the power-off condition. The alarm state before the power-off will be maintained at the next power-on to prevent the alarm from being invalid due to power failure, reset, etc.

  ● Suitable for 0.4kV voltage class TN-C-S, TN-S and local TT system.

  4.1.2 Technical parameters



  4.1.3 Terminal Blocks



  4.2 ARCM200BL-J1, ARCM200BL-J4, ARCM200L-J8 monitoring detector

  4.2.1 Features

  ● It can monitor multiple leakage currents and temperature signals of each phase cable online;

  ● Rated residual current action value, trip delay, can be flexibly set according to needs, temperature action value is also programmable;

  ● Screen persistence function, when the leakage fault occurs, the channel display screen is paused, indicating the value of the channel leakage or over-temperature, which is convenient for the fault record of the host computer;

  ● With fieldbus communication technology, the host computer management software can monitor the operation of the site at all times and discover the alarm information in time. The standard MODBUS protocol can be connected to various standard systems via the RS485 interface;

  ● ARCM200L-J1 and ARCM200L-J4 have event storage function. The alarm can record the time, type and parameters of the alarm. According to the alarm record, the power consumption of the site can be analyzed to provide a basis for eliminating the fault.

  ● High integration, network, high degree of intelligence, and reasonable action characteristics;

  ● Suitable for 0.4kV voltage class TN-C-S, TN-S and local TT system.

  4.2.2 Technical parameters



  4.2.3 Terminal Blocks

  ♦ARCM200BL-J1, ARCM200BL-J4



        ♦ARCM200L-J8


  4.3 ARCM300 type monitoring detector

  4.3.1 Features

  ● It can monitor single or multi-channel leakage current, temperature signal of each phase cable, and each channel has disconnection and short circuit detection functions;

  ● Rated residual current action value, trip delay and action type can be flexibly set as required;

  ● Standard 35mm rail mounting, LCD or LED display;

  ● Screen persistence function, when the leakage fault occurs, the channel display screen is reserved, indicating the value of leakage or over-temperature of the channel, which is convenient for the fault record of the host computer;

  ● With event storage function, the alarm can record the time, type and parameter of the alarm occurrence. According to the alarm record, the power consumption of the site can be analyzed to provide a basis for eliminating the fault.

  ● With fieldbus communication technology, the host computer management software can monitor the operation of the site at all times and discover the alarm information in time. The standard MODBUS protocol can be connected to various standard systems via the RS485 interface;

  ● High integration, network, high degree of intelligence, and reasonable action characteristics;

  ● Suitable for 0.4kV voltage class TN-C-S, TN-S and local TT system.

  4.3.2 Technical parameters


  4.3.3 Outline and installation dimensions (mm)

  Dimensions;


  Installation method:



  4.3.4 Terminal Blocks



  4.4 ARCM200L-I, ARCM200L-UI, ARCM200L-Z, ARCM200L-Z2 monitoring detector

  4.4.1 Features

  ● Real-time monitoring of one channel of residual current, one way temperature. Optional three-phase current, three-phase voltage, frequency, power, four-quadrant power and other electrical parameters monitoring (see instrument selection);

  ● With residual current protection and temperature protection. Optional over-current protection, over-voltage protection, phase loss protection and other protection functions (see instrument selection);

  ● Provide two-way switch input function, one-way switch feedback signal, all the way to do fire linkage signal;

  ● Provide two relay output functions, one for alarm output and one for trip output;

  ● With event storage function, the alarm can record the time, type and parameter of the alarm occurrence, and can analyze the scene according to the alarm record to provide a basis for eliminating the fault;

  ● With fieldbus communication technology, the host computer management software can monitor the operation of the site at all times and discover the alarm information in time. The standard Modbus protocol can be connected to various standard systems via the RS485 interface;

  ● High integration, network, high degree of intelligence, and reasonable action characteristics;

  ● Suitable for 0.4kV voltage class TN-C-S, TN-S and local TT system.

  Note: ARCM200L-I: Three-phase current monitoring, overcurrent protection

  ARCM200L-UI: Three-phase voltage and current monitoring, overvoltage, phase loss, overcurrent protection

  ARCM200L-Z: Three-phase voltage, current, power, frequency, four-quadrant power monitoring, overvoltage, phase loss, overcurrent protection

  ARCM200L-Z2: Three-phase voltage, current, power, frequency, four-quadrant power monitoring, overvoltage, phase loss, overcurrent protection

  4.4.2 Technical parameters



  4.4.3 Terminal Blocks




  4.5 ARCM500-J32 Electrical Fire Monitoring Detector

  4.5.1 Features

  ● Cooperate with AKH-0.66LXXD and ARCM200/300, support up to 32 loop residual current and 96 loop temperature monitoring, and build a small electrical fire monitoring system;

  ● The rated residual current action value, temperature action value and action delay can be flexibly set according to requirements, and the monitoring unit performs alarm protection according to the set value;

  ● The monitoring unit has relay protection output, which can realize remote sound and light alarm function;

  ● With event storage function, the monitoring unit can record the time, location and alarm parameters of the alarm. According to the alarm record, the insulation condition of the site can be analyzed to provide a basis for eliminating the fault.

  ● With fieldbus communication technology, the host computer management software can monitor the operation of the site at all times and send alarm information in time. The standard MODBUS protocol can be connected to various standard systems via the RS485 interface;

  ● Suitable for 0.4kV voltage class TN-C-S, TN-S and local TT system.


  4.5.2 Technical parameters


  5 accessory accessories

  5.1 AKH-0.66L Series Analog Residual Current Transformer

  5.1.1 Product appearance


  5.1.2 Transformer Selection Table


  5.2 AKH-0.66LXXD Series Digital Residual Current Transformer

  5.2.1 Features

  ● Real-time monitoring of residual current in single circuit, and alarming according to settings;

  ● Rated residual current action value and action delay can be flexibly set as needed;

  ● The digital processing module is directly embedded in the transformer, which realizes digitization of the transformer and high signal reliability.

  ● With event storage function, the alarm can record the time and parameters of the alarm occurrence. According to the alarm record, the insulation condition of the site can be analyzed to provide a basis for eliminating the fault.

  ● With fieldbus communication technology, the host computer management software can monitor the operation of the site at all times and discover the alarm information in time. The standard MODBUS protocol can be connected to various standard systems via the RS485 interface;

  ● Suitable for 0.4kV voltage class TN-C-S, TN-S and local TT system.


  5.2.2 Technical parameters

  5.2.3 Transformer Selection Table

  5.3 ARCM-NTC temperature sensor