Acrel-6000/B Electrical Fire Monitoring System at Hangzhou Science and Technology Park, Singapore
时间: 2018-10-13 08:15 浏览次数: 来源:安科瑞智能照明控制系统

  Abstract: Large-scale public buildings, commercial buildings are densely staffed, and social attention is high. The prevention of electrical fires is very important. In view of the characteristics of densely populated areas such as commercial office buildings, large shopping malls, living quarters, infrastructure, shopping malls, etc., the state and various regions have formulated mandatory regulations for electrical fire prevention. The installation of an electrical fire monitoring system in various personnel-intensive locations as described above can effectively prevent the occurrence of electrical fires. This paper introduces the application of Ankerui Acrel-6000/B electrical fire monitoring system in the data processing plant A and B projects of Hangzhou Science and Technology Park in Singapore, analyzes relevant national standards and design specifications, and outlines electrical fire monitoring systems in electrical fire prevention. The specific structure of the aspect and its superiority.

  Key words: factory building; electrical fire; Hangzhou Science and Technology Park, Singapore; Ankerui;

  Foreword

  In the past ten years of fire accidents, electrical fires ranked first, and the average number of occurrences accounted for 27% of the total number of fires per year, accounting for 80% of the total number of major fires, and the loss accounted for 53% of the total fire damage. In developed countries, the number of electrical fires per year accounts for 8% to 13% of the total number of fires. In fact, electrical fires have become the main cause of fire safety, not only in many times, but also in large losses, and have remained high for many years. Commercial hotel personnel are intensive, fluid, and publicly concerned, and the prevention of electrical fires in their distribution systems is even more important.

  Electrical fire prevention in the factory has the following main aspects:

  (1) Electrical fires generally start in electrical cabinets, cable trays, etc. When the fire spreads to the surface of the equipment and cables, a large fire has formed. At this time, the fire is often not easily controlled, so prevention is very important.

  (2) The workshops and office buildings are highly intensive and have many flammable materials. If a fire breaks out, it is likely to cause casualties.

  The Acrylic-Acrel-6000/B electrical fire monitoring system independently developed by Ankerui Electric Co., Ltd. can monitor the leakage current and other parameters of each important circuit in real time to prevent electrical fires. The background of the system displays the data of each detection point, and also provides functions such as over-limit sound and light alarm and humanized interface. The system realizes 24-hour unattended real-time monitoring of the power distribution system, reduces labor costs, and improves the elimination efficiency of electrical fire hazards.

  This paper briefly introduces the practical application of the Acry-6000/B electrical fire system and its practical significance in the application of the electrical fire system in the electrical fire monitoring system project of the data processing plant A and B in Hangzhou Science and Technology Park, Singapore.

  1 Project Overview

  The data processing plant A and B of Hangzhou Science and Technology Park in Singapore is located at No. 19, Xiasha 6th Street, Jianggan District, Hangzhou City, Zhejiang Province. An electrical fire monitoring system is designed for the data processing plants A and B of the Hangzhou Science and Technology Park in Singapore to monitor the leakage current and other electrical parameters of the distribution circuit to ensure the electrical safety of the entire distribution system.

  For the characteristics of this project, the ARCM series residual current electrical fire monitoring detector developed by Ankerui is installed in the important circuit of the power distribution cabinet on some floors. The electrical fire monitoring system shall monitor the residual current value of the important circuit and the real-time temperature of the tank circuit in real time. The monitored data will be transmitted to the background host in real time. When the residual current value exceeds the limit and the temperature exceeds the limit, the background can perform sound and light alarm. The background can be linked to the fire alarm system.

  2 reference standard

  In view of the fire in public buildings, it is easy to cause loss of life and property. In order to increase the intensity of electrical fire monitoring and prevention, in recent years, the state has successively formulated or revised a number of relevant standards and norms. The relevant standard specifications have put forward specific requirements for the electrical fire monitoring system. The design standards for the design of the Acrylic-Acrel-6000/B electrical fire system selected in this project are as follows:

  2.1 GB50045-95 (2005 edition) "Code for Fire Protection Design of High-rise Civil Buildings", which stipulates in Article 9.5.1 that a fire alarm system should be installed in places with high fire risk and dense personnel in high-rise buildings.

  2.2 The relevant provisions of the national standard "Building electrical fire prevention requirements and testing methods" also clearly require that "the residual current action protector that automatically cuts off the power or alarm should be set at the power incoming end."

  2.3 The products of the electrical fire monitoring system shall meet: GB14287.1-2005 "Electrical fire monitoring equipment", GB14287.2-2005 "Residual current type electric fire monitoring detector", GB14287.3-2005 "Temperature type electric fire monitoring" detector"

  2.4 The installation and operation of the electrical fire monitoring system shall meet the requirements of GB13955-2005 "Installation and operation of residual current action protection device"

  2.5 The power supply of the electrical fire monitoring system shall meet the requirements of GB50052 "Design Specifications for Power Supply and Distribution Systems"

  2.6 The design of the electrical fire monitoring system shall meet the requirements of the Design Method of Electrical Fire Monitoring System (Interim Provisions)

  3 system architecture and design

 

   Electrical fire monitoring system topology

  3.1 Station management

  The management of the station control management system for the electrical fire monitoring system is the direct window of human-computer interaction and the uppermost part of the system. The Encore Electric Fire Monitoring System mainframe fully takes into account the user's operating habits and continuous and stable operation, with reference to the corresponding national standards and specifications. The host computer is mainly composed of monitoring software, touch screen, UPS power supply, printer and other equipment. The various types of data information on the site are calculated, analyzed, and processed, and reacted to the terminal management personnel in the form of graphics, digital display, sound, and indicator lights. Enables managers to grasp system dynamics in real time, and realizes functions such as fault information can be traced and information can be exported.

  In view of the instrument point and the amount of data in this project, the Acrylic-Acrel-6000/B host is now configured for the project. The specific parameters of this host are described below.

  3.2 Network communication layer

  All instruments in this project must be connected in strict accordance with the hand, and all communication buses must be laid along the weak bridge. The instrument of this project is distributed in the electrical fire monitoring and detection between the floors of the strong electricity.

  The data bus of this project is designed as two buses. The independent bus facilitates the maintenance of the later system. When a leakage current alarm occurs, the fault circuit can be quickly located according to the checklist provided by us in the later stage to quickly eliminate the fault.

  The on-site electrical fire detectors are connected by hand in a twisted pair (ZR-RVSP2*1.0), and the number of meters per bus is about 20.

  3.3 Field device layer

  In this project, the Ankerui embedded electrical fire detector is installed for the incoming circuit of the floor distribution box. The embedded electric fire detector monitors the leakage current of the distribution circuit in real time to display the working status of the entire distribution system. .

  The ARCM series residual current type electrical fire monitoring detector is designed for TT and TN systems below 0.4kV. It monitors and manages the fire risk parameters such as residual current, wire temperature, over current and over voltage of the distribution circuit. Thereby preventing the occurrence of electrical fires and real-time monitoring of various power parameters, providing accurate data for energy management. The product adopts advanced microcontroller technology, with high integration, small size, convenient installation, intelligent, digital and networked. It is an ideal choice for building electrical fire prevention monitoring and system insulation aging prediction. The product complies with the standard requirements of GB14287.2-2005 "Electrical Fire Monitoring System Part 2: Residual Current Electrical Fire Monitoring Detector".

  4 system characteristics and working principle

  4.1 System Features

  In view of the scale of the project, as well as the actual situation of the electrical fire detection points of the project. Whether in the terminal residual current detector or the background host is designed according to the actual situation of the project.

  The system characteristics of this project can be summarized as follows:

  4.1.1 The terminal detector uses embedded electrical fire detector to facilitate installation, save cost and facilitate post-maintenance.

  4.1.2 RS485 bus connection is convenient and operability is strong. When the bus is routed, it is a weak bridge, which is not affected by strong electricity, ensuring stable communication of the entire system.

  4.1.3 Taking into account the amount of instrument data in this project, customer requirements. The host of this project is wall-mounted. The wall-mounted host has a simple interface and is easy to operate. It is suitable for the distribution room environment and customer related operation requirements in this project.

  4.2 Working principle:

  4.2.1 The residual current measurement is based on Kirchhoff's current law: at the same time, the sum of the current vectors flowing into and out of a node in the circuit is zero. Taking the TN-S system as an example, A/B/C/N is simultaneously passed through the residual current transformer. When there is no leakage in the system, the current vector sum of the residual current transformer flowing into and out is zero. At this time, the residual current The secondary current induced by the transformer is also 0; when a relatively large earth leakage occurs, the current vector sum of the current transformer flowing into and out of the residual current is no longer zero, and its magnitude is equal to the current flowing from the earth, that is, the leakage current. The leakage signal is transmitted to the electrical fire detector through the secondary wiring of the residual current transformer, and is sent to the CPU after operation amplification, A/D conversion, and after a series of algorithms, the amplitude of the change is analyzed and judged, and The alarm set value is compared. If the set value is exceeded, an audible and visual alarm signal is sent and sent to the background electrical fire monitoring device.

  4.2.2 The terminal detector is responsible for monitoring the residual current value of each loop and transmitting the data of the residual current value to the system host. The terminal detector is also responsible for the real-time display of the residual current value of the monitoring circuit, and can set the limit value. When the residual current value exceeds the limit, it can emit an audible and visual alarm to remind the management personnel to maintain and rectify in time.

  4.2.3 The instrument transmits data to the system host through RS485 bus. The system host reflects the running status of the whole system through graphs, reports, event records and other forms.

  5 System design considerations and methods

  5.1 Electrical fire monitoring system mainly monitors two types of objects, residual current and temperature, and should pay attention to the basic points in design.

  5.1.1 About residual current

  Since the principle of residual current monitoring uses Kirchhoff's current law, there are certain requirements for the form of the low-voltage power distribution system to be applied. At present, low-voltage power distribution systems that can apply residual current transformers are: TT system, IT system, TN-S system, and cannot be used in TN-C system. For users who will design and install an electrical fire monitoring system, whether it is a new project or an old engineering project, first check the system grounding form of the user's low-voltage power distribution system. Otherwise, design and install the residual current transformer. Detection is simply not possible.

  Regarding the AC220V single-phase power supply system, the residual current transformer only needs to cover the L/N power lines, but the neutral line N is not allowed to be grounded again. For the AC380V three-phase power supply system, due to the three-phase three-wire system, three-phase four-wire system, three-phase five-wire system, etc., the residual current transformer is simultaneously sheathed to the A/B/C three-phase power line according to the specific situation. Or cover the A/B/C/N line at the same time. Similarly, the neutral line N is not allowed to be grounded again, and the protection line PE must not pass through the transformer.

  When the system grounding type is TN-C type, the industrial automation network must be converted into a TN-S type, TN-C-S type or partial TT type system before the residual current detecting device can be installed.

  5.1.2 About temperature

  Temperature measurement has nothing to do with the form of system grounding. It mainly considers the temperature of key parts of low-voltage power distribution equipment including cables, and is generally applied in secondary protection lines. The temperature probe Pt100 can adopt the contact arrangement method. When the object to be detected is an insulator, the temperature sensor of the detector should be directly disposed on the surface of the object to be detected. When the object to be tested is the temperature change inside the power distribution cabinet, a non-contact arrangement can be adopted, which is close to the heat generating component.

  5.2 Point allocation in system design

  According to the national standard GB13955-2005 "Residual current action protection device installation and operation" in the provisions of 4.4 on the classification protection, when installing the residual current fire monitoring device, the steps of the point allocation principle are:

  5.2.1 Study and analyze the relevant drawings of the controlled low-voltage AC380V/220V distribution line, investigate and verify the distribution of building electrical, and determine the location of power distribution equipment (such as power distribution cabinets, boxes, disks, cables, etc.). Each monitoring detector is assigned to the corresponding power distribution equipment to determine the number of detectors and avoid resetting waste.

  5.2.2 Determine the hierarchical protection. In order to reduce the range of power failure caused by the occurrence of personal electric shock accidents and ground faults, three-stage (or two-stage) residual current protection devices of different capacities are usually installed at different locations of the power supply line to form hierarchical protection. According to the power load and line conditions, it is generally divided into two or three levels of protection, suitable for urban and rural first and second level protection. Among them, important routes should include security, fire, emergency power, channel lighting and important places that do not allow power outages.

  5.2.3 In the secondary protection, all the switches shall be equipped with a residual current fire monitoring detector, that is, at the power supply end of the line (first level protection) and the branch head end (second stage also called end protection). Install the residual current detector and connect it to the electrical fire monitoring system for fire monitoring and alarming purposes only.

  5.2.4 Temperature detection is based on the basic principle that heat is generated when the power distribution equipment is abnormal.

  1) Transformer low-voltage side outlet terminal, transformer body temperature (wind temperature, oil temperature, water temperature) test point, load switch contact.

  2) Incoming and outgoing busbar contacts, automatic switch (circuit breaker, knife switch) contacts, large current conductor concentrated parts, and cable docking points of each power distribution cabinet (box).

  3) The main joint of the female joint cabinet and the switch contacts of the knife.

  4) Compensation capacitor terminal and transfer switch contact.

  5) According to the total number of points installed, select the corresponding wall hanging, vertical or piano.

  6 System parameter configuration

  6.1 Alarm value setting range

  The residual current alarm value of the field instrument in this project is set at 300 mA. The setting of the residual current value is detailed in the relevant national standards.

  According to the national standard GB14287.2-2005, the alarm value of the residual current type electrical fire monitoring detector is set between 20~1000mA. According to this requirement, the residual current action value at the power supply main line is generally set to 400~800mA, and the residual current action value on the power branch line is set to 100~400mA. Generally, the residual current type electrical fire monitoring detection is set at the actual site. The alarm value of the device shall not be less than 2 times the maximum value of the leakage current during normal operation of the protected electrical circuit and equipment, and not more than 1000 mA. The alarm setting value of the electrical fire detector should take into account the normal leakage current of the power distribution system and the electrical equipment.

  6.2 Refer to the cable temperature rise alarm setting reference, according to the "Power Cable Design Specification" for cable temperature requirements

  1) For high temperature places above 60 °C, heat-resistant cables such as heat-resistant PVC, XLPE or Ethylene-propylene rubber insulation should be used according to the requirements of high temperature, duration and insulation type. Mineral insulation should be used at temperatures above 100 °C. cable. It is not advisable to use ordinary PVC insulated cables in high temperature places.

  2) The ambient temperature of the continuous allowable current carrying capacity of the cable shall be determined according to the multi-year average of the meteorological temperature of the area of ​​use and shall comply with the regulations. When the indoor cable trench is laid, the ambient temperature is the average daily maximum temperature of the hottest month of the site plus 5 °C.

  3) The temperature rise of the cable is related to the laying and heat dissipation conditions.

  7 main equipment parameters

 

  The electrical fire monitoring system of the Baozhaolong Library Project of Shanghai Jiaotong University consists of the electrical fire monitoring device Acrel-6000/B, the leakage fire detector ARCM200L-J1, and the leakage current transformer AKH-0.66L. There are not many introductions about instruments and transformers. The relevant information can be found on the official website of http://www.acrel.cn.

  7.1 main technical parameters

  power supply:

  1) Rated working voltage AC220V (-15% ~ +10%)

  2) Backup power supply: When the main power supply is under voltage or power failure, maintain the monitoring equipment working time ≥ 4 hours

  Working system:

  24-hour work schedule

  communication method:

  RS485 bus communication, Modbus-RTU communication protocol, transmission distance 1.2km, can extend communication transmission distance through repeater

  Monitoring capacity:

  1) Monitoring equipment can monitor up to 1024 (customized) monitoring units (detectors)

  2) can be connected to ARCM series monitoring detector

  Monitoring alarm items:

  1) Residual current fault (leakage): fault unit attribute (part, type)

  2) Temperature alarm (over temperature): Fault unit attribute (part, type)

  3) Current fault (overcurrent): Fault unit attribute (part, type)

  Monitoring alarm response time: ≤30s

  Monitoring alarm sound pressure level (A weighting): ≥70dB/1m

  Monitoring alarm light display: red LED indicator, red light alarm signal should be maintained until manual reset

  Monitoring alarm sound signal: can be manually eliminated, can be started again when there is alarm signal input again

  Fault alarm item:

  1) The communication cable between the monitoring device and the detector is broken or shorted.

  2) Monitoring equipment main power supply undervoltage or power failure

  3) The connection between the charger that charges the battery and the battery is broken or shorted.

  Fault alarm response time: ≤100s

  Monitoring alarm sound pressure level (A weighting): ≥70dB/1m

  Monitoring alarm light display: yellow LED indicator, yellow light alarm signal should be kept until troubleshooting

  Fault alarm sound signal: can be manually eliminated, can be started again when there is an alarm signal input again

  The normal operation of the non-faulty loop is not affected during the fault

  Control output:

  Alarm control output: 1 set of normally open passive contacts, capacity: AC250V 3A or DC30V 3A

  Self-test items:

  Indicator check:

  1) Alarm, fault, operation, main power, standby power indicator

  2) Display check

  3) Audio device inspection

  Self-test time ≤60s

  record:

  1) Recording content: record type, time of occurrence, detector number, area, fault description, can store no less than 20,000 records

  2) Record query: query according to the date, type and other conditions of the record

  Operational rating:

  Environmental conditions used:

  7.2 basic functions

  The monitoring equipment can receive the leakage and temperature information of multiple detectors, and emit an audible and visual alarm signal when the alarm occurs. At the same time, the red “alarm” indicator on the device lights up, the display indicates the alarm location and alarm type, and the alarm time is recorded. The sound and light alarm is always maintained. Until the display is reset by pressing the display "Reset" button. The audible alarm signal can also be manually removed using the display "Muffler" button.

  2. Fault alarm function

  Communication failure alarm: When a communication failure occurs between the monitoring device and any of the connected detectors, the corresponding detector in the monitoring screen displays a fault indication, and the yellow “fault” indicator on the device lights up, and a fault alarm sound is emitted. .

  a Power failure alarm: When the main power or backup power fails, the monitoring device also emits an audible and visual alarm signal and displays the fault information. You can enter the corresponding interface to view detailed information and release the alarm sound.

  b Self-test function: Check whether all status indicators, display and speakers in the device are normal.

  c alarm record storage query function

  When leakage, over-temperature alarm or communication or power failure occurs, the alarm part, fault information, alarm time and other information are stored in the database. When the alarm is cancelled or the fault is eliminated, the same is recorded. Historical data provides a variety of convenient and fast ways to query.

  3. Power function

  When the main power supply has a power failure, undervoltage, etc., the monitoring equipment can automatically switch to the standby power supply. When the main power supply returns to normal power supply, it automatically switches back to the main power supply, ensuring continuous and smooth operation of the monitoring equipment during the switching process.

  4. Detector control function

  Remote monitoring of all detectors connected to the unit is possible through monitoring software operation.

  5. Authority control function

  In order to ensure the safe operation of the monitoring system, the monitoring device software operation authority is divided into three levels, and different levels of operators have different operation rights.

  8 Project Summary

  With the intelligent development of intelligent buildings and power systems, the government and the public have become more and more aware of the electrical safety of power systems. The installation of leakage fire systems in enterprise buildings, public buildings and commercial buildings is an inevitable trend of intelligent construction. The electrical fire system is conducive to the detection of potential safety hazards, promptly reminding managers to deal with potential safety hazards, and has important significance for fire prevention. Since the system was put into operation in the data processing plant A and B of Hangzhou Science and Technology Park in Singapore, the system has helped Party A to discover and rectify many electrical safety hazards, greatly improving the work efficiency of the staff and ensuring the stable and orderly work of the daily work of the plant. The operation ensures the safe operation of the plant and provides a scientific basis for the fire management of the plant.

  The whole process of designing, installing, commissioning and accepting the electrical fire system is not only a comprehensive inspection of electrical safety, but also a comprehensive training for the users of the distribution system. Through the implementation of the project and the training of the system, the project is made. The power system management personnel can more thoroughly understand the troubleshooting methods of electrical fire hazards in the distribution system of the project, and improve their awareness and efficiency of electrical fire prevention.

  After the project is running normally, we also provide the complete set of information of the electrical fire system of the project. The data includes the point table of the electrical fire detection point of the project and the system instruction manual. For the point table, the specific name position of each fire detector installation circuit in this project is marked above, and the real-time data after the normal operation of the system. The complete set of materials facilitates the later management personnel to quickly master the system architecture, improve system maintenance efficiency and troubleshooting speed.

  references

  [1]. Ren Zhicheng Zhou Zhong. Principles and Application Guidelines of Power Electrical Measurement Digital Instrumentation [M]. Beijing. China Electric Power Press. 2007. 4

  [2]. Zhou Zhong. Application of power meter in electric energy metering of large commercial hotels [J]. Modern Building Electric 2010. 6

上一篇:Acrel-6000 electrical fire monitoring system in the second annex of Mudanjiang Medical College
下一篇:Acrel-6000 electrical fire monitoring system in Jingbo Agrochemical Technology Co., Ltd.

安科瑞电子商务(上海)有限公司

咨询热线:021-69157502  手机:187-0211-2013

传真:021-69158302  地址:上海市嘉定区育绿路253号

主要销售地区:上海,北京,广东,山东

公司自成立以来一直专注于用户端智能电力仪表的研发应用、生产和销售,致力于为用户提供电能质量治理、电能分项计量、
电气火灾监控系统包括多用户计量箱、电气火灾监控、智能照明控制、能耗监测系统、预付费电力系统等   网站地图-XML